Backflow assembly test · 7375 Cedar Hollow Ln

Approved

Filed Jan 28, 2025 by Shawn Hollins, Ridge Plumbing & Backflow · paper form read in and confirmed by staff

Report

Date of service
Jan 28, 2025
Assembly type
DC
Serial number
A510570
Size
1
Test gauge serial
G-3971
Gauge calibration date
May 25, 2024
Check valve 1
7.1 psid
Check valve 1 closed tight
Yes
Check valve 2
1.8 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 013-11-01034
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

7375 Cedar Hollow Ln
Owner: Reese Vance
Parcel 013-11-01034