Boulder County, COCompliance reporting portal
Demo · made-up dataOpen the pro appChange county
← Backflow review queue

Backflow assembly test · Maple Leaf Taqueria

Approved

Filed Nov 2, 2026 by Drew Fairley, Evergreen Backflow Testing · filed from phone

Report

Date of service
Nov 2, 2026
Assembly type
RP
Serial number
Z935307
Size
1 1/2
Test gauge serial
G-7973
Gauge calibration date
Aug 9, 2026
Check valve 1
6.8 psid
Check valve 1 closed tight
Yes
Check valve 2
3.5 psid
Relief valve opened at
3.5 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 013-57-01081
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

5855 Orchard Ln
Owner: Harlow Holdings LLC
Parcel 013-57-01081