← Backflow review queue
Backflow assembly test · 9366 Quarry Ln
ApprovedFiled Aug 10, 2025 by Drew Fairley, Evergreen Backflow Testing · filed from phone
Report
- Date of service
- Aug 10, 2025
- Assembly type
- PVB
- Serial number
- Z587091
- Size
- 3/4
- Test gauge serial
- G-4922
- Gauge calibration date
- Feb 25, 2025
- Check valve 1
- 7.1 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 3.9 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 013-93-01262
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by Auto-approved (no flags). The property's next due date is set and the owner gets a receipt.
Property
9366 Quarry Ln
Owner: Quinn Stroud
Parcel 013-93-01262