← Backflow review queue
Backflow assembly test · 3782 Stone Gate Way
ApprovedFiled Dec 10, 2023 by Drew Fairley, Evergreen Backflow Testing · filed from phone
Report
- Date of service
- Dec 10, 2023
- Assembly type
- RP
- Serial number
- K639677
- Size
- 1
- Test gauge serial
- G-4524
- Gauge calibration date
- Jun 18, 2023
- Check valve 1
- 0.6 psid
- Check valve 1 closed tight
- No
- Check valve 2
- 1.7 psid
- Relief valve opened at
- 3.8 psid
- Result
- Fail
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 013-40-01173
- Readings in range, no flags
- Result: needs follow-up. The property stays on the overdue list until a passing report arrives.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.
Property
3782 Stone Gate Way
Owner: Casey Hollins
Parcel 013-40-01173