Boulder County, COCompliance reporting portal
Demo · made-up dataOpen the pro appChange county
← Backflow review queue

Backflow assembly test · 3782 Stone Gate Way

Approved

Filed Dec 10, 2023 by Drew Fairley, Evergreen Backflow Testing · filed from phone

Report

Date of service
Dec 10, 2023
Assembly type
RP
Serial number
K639677
Size
1
Test gauge serial
G-4524
Gauge calibration date
Jun 18, 2023
Check valve 1
0.6 psid
Check valve 1 closed tight
No
Check valve 2
1.7 psid
Relief valve opened at
3.8 psid
Result
Fail
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 013-40-01173
  • Readings in range, no flags
  • Result: needs follow-up. The property stays on the overdue list until a passing report arrives.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

3782 Stone Gate Way
Owner: Casey Hollins
Parcel 013-40-01173