Backflow assembly test · Corner Self Storage
ApprovedFiled Sep 6, 2025 by Shawn Hollins, Summit Plumbing & Backflow · filed from phone
Report
- Date of service
- Sep 6, 2025
- Assembly type
- RP
- Serial number
- W366314
- Size
- 1
- Test gauge serial
- G-5457
- Gauge calibration date
- Jul 21, 2025
- Check valve 1
- 0.6 psid
- Check valve 1 closed tight
- No
- Check valve 2
- 2.9 psid
- Relief valve opened at
- 4.2 psid
- Result
- Fail
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 014-26-01249
- Readings in range, no flags
- Result: needs follow-up. The property stays on the overdue list until a passing report arrives.
Decision
Approved by J. Staff. The property's next due date is set and the owner gets a receipt.
Property
1806 Turkey Hill Trl
Owner: Calloway Holdings LLC
Parcel 014-26-01249