Broomfield County, COCompliance reporting portal
Demo · made-up dataOpen the pro appChange county
← Backflow review queue

Backflow assembly test · 3888 Stone Gate Dr

Approved

Filed Jul 5, 2024 by Jamie Ramirez, Patriot Backflow Testing · filed from phone

Report

Date of service
Jul 5, 2024
Assembly type
RP
Serial number
W399531
Size
1
Test gauge serial
G-3396
Gauge calibration date
Jun 1, 2024
Check valve 1
0.7 psid
Check valve 1 closed tight
No
Check valve 2
2.5 psid
Relief valve opened at
4.1 psid
Result
Fail
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 014-14-01063
  • Readings in range, no flags
  • Result: needs follow-up. The property stays on the overdue list until a passing report arrives.

Decision

Approved by Auto-approved (no flags). The property's next due date is set and the owner gets a receipt.

Property

3888 Stone Gate Dr
Owner: Drew Whitcomb
Parcel 014-14-01063