Backflow assembly test: 2998 Pine Knoll Ct

Approved

Filed Aug 15, 2025 by Reese Stroud, Evergreen Backflow Testing. Filed from a phone.

Report

Date of service
Aug 15, 2025
Assembly type
RP
Serial number
Z181432
Size
1
Test gauge serial
G-4517
Gauge calibration date
Dec 25, 2024
Check valve 1
6.6 psid
Check valve 1 closed tight
Yes
Check valve 2
1.2 psid
Relief valve opened at
3.7 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Reese Stroud, current on the service date
  • All required fields present
  • Address matches parcel 014-75-01121
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

2998 Pine Knoll Ct
Owner: Drew Kessler
Parcel 014-75-01121