Backflow assembly test · 1836 Quarry Ln
ApprovedFiled Aug 16, 2025 by Jamie Ramirez, Patriot Backflow Testing · filed from phone
Report
- Date of service
- Aug 16, 2025
- Assembly type
- RP
- Serial number
- A956695
- Size
- 1
- Test gauge serial
- G-7837
- Gauge calibration date
- May 23, 2024
- Check valve 1
- 0.7 psid
- Check valve 1 closed tight
- No
- Check valve 2
- 2.4 psid
- Relief valve opened at
- 2.7 psid
- Result
- Fail
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 014-17-01198
- Test gauge calibration is more than a year old.
- Result: needs follow-up. The property stays on the overdue list until a passing report arrives.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.
Property
1836 Quarry Ln
Owner: Alex Kessler
Parcel 014-17-01198