Broomfield County, COCompliance reporting portal
Demo · made-up dataOpen the pro appChange county
← Backflow review queue

Backflow assembly test · Blue Heron Grill

Approved

Filed Aug 3, 2026 by Reese Stroud, Evergreen Backflow Testing · filed from phone

Report

Date of service
Aug 3, 2026
Assembly type
RP
Serial number
B148728
Size
4
Test gauge serial
G-8528
Gauge calibration date
Apr 11, 2026
Check valve 1
8.4 psid
Check valve 1 closed tight
Yes
Check valve 2
3.1 psid
Relief valve opened at
2.6 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 014-57-01161
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.

Property

3840 Quarry Rd
Owner: Wexler Holdings LLC
Parcel 014-57-01161