Backflow assembly test · Blue Heron Self Storage

Approved

Filed Oct 3, 2025 by Reese Stroud, Evergreen Backflow Testing · filed from phone

Report

Date of service
Oct 3, 2025
Assembly type
RP
Serial number
B151018
Size
1 1/2
Test gauge serial
G-3826
Gauge calibration date
Jun 21, 2025
Check valve 1
5.4 psid
Check valve 1 closed tight
Yes
Check valve 2
2.1 psid
Relief valve opened at
3.6 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 014-61-01353
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by Auto-approved (no flags). The property's next due date is set and the owner gets a receipt.