Backflow assembly test · Main Street Grill
ApprovedFiled May 25, 2025 by Logan Wexler, Patriot Plumbing & Backflow · paper form read in and confirmed by staff
Report
- Date of service
- May 25, 2025
- Assembly type
- RP
- Serial number
- B375413
- Size
- 2
- Test gauge serial
- G-6243
- Gauge calibration date
- Aug 6, 2024
- Check valve 1
- 0.3 psid
- Check valve 1 closed tight
- No
- Check valve 2
- 3.8 psid
- Relief valve opened at
- 3.3 psid
- Result
- Fail
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 031-59-01336
- Readings in range, no flags
- Result: needs follow-up. The property stays on the overdue list until a passing report arrives.