Backflow assembly test · Corner Apartments
ApprovedFiled Jul 19, 2025 by Parker Benton, Keystone Plumbing & Backflow · filed from phone
Report
- Date of service
- Jul 19, 2025
- Assembly type
- DC
- Serial number
- A834297
- Size
- 4
- Test gauge serial
- G-6532
- Gauge calibration date
- Nov 14, 2024
- Check valve 1
- 6.1 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 3.6 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 031-26-01295
- Readings in range, no flags
- Result: passing. Next due date resets when approved.