← Backflow review queue
Backflow assembly test · 3286 Turkey Hill Ct
ApprovedFiled Oct 10, 2026 by Logan Nguyen, Keystone Plumbing & Backflow · filed from phone
Report
- Date of service
- Oct 10, 2026
- Assembly type
- PVB
- Serial number
- K138745
- Size
- 3/4
- Test gauge serial
- G-1925
- Gauge calibration date
- Jun 4, 2026
- Check valve 1
- 6.1 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 2.9 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 031-53-01236
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by J. Staff. The property's next due date is set and the owner gets a receipt.
Property
3286 Turkey Hill Ct
Owner: Parker Whitcomb
Parcel 031-53-01236