← Backflow review queue
Backflow assembly test · 3678 Laurel Ct
ApprovedFiled Jun 7, 2026 by Logan Wexler, Patriot Plumbing & Backflow · filed from phone
Report
- Date of service
- Jun 7, 2026
- Assembly type
- PVB
- Serial number
- K719776
- Size
- 3/4
- Test gauge serial
- G-1677
- Gauge calibration date
- Sep 9, 2025
- Check valve 1
- 3.9 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 2.4 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 031-37-01249
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by Auto-approved (no flags). The property's next due date is set and the owner gets a receipt.
Property
3678 Laurel Ct
Owner: Logan Whitcomb
Parcel 031-37-01249