Backflow assembly test · Maple Leaf Pizza
ApprovedFiled Sep 21, 2026 by Logan Wexler, Patriot Plumbing & Backflow · filed from phone
Report
- Date of service
- Sep 21, 2026
- Assembly type
- DC
- Serial number
- K609420
- Size
- 2
- Test gauge serial
- G-8808
- Gauge calibration date
- Nov 14, 2025
- Check valve 1
- 4.5 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 2.1 psid
- Result
- Repaired and passed
- Repairs made
- Replaced check valve 1 rubber
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 031-76-01354
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by J. Staff. The property's next due date is set and the owner gets a receipt.