Douglas County, COCompliance reporting portal
Demo · made-up dataOpen the pro appChange county
← Backflow review queue

Backflow assembly test · 1229 Orchard Trl

Approved

Filed Apr 2, 2025 by Quinn Okafor, Ridge Backflow Testing · filed from phone

Report

Date of service
Apr 2, 2025
Assembly type
PVB
Serial number
A143833
Size
1
Test gauge serial
G-9918
Gauge calibration date
Jul 23, 2024
Check valve 1
8.9 psid
Check valve 1 closed tight
Yes
Check valve 2
2.2 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 035-49-01296
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.

Property

1229 Orchard Trl
Owner: Emerson Ramirez
Parcel 035-49-01296