← Backflow review queue

Backflow assembly test · 8162 Spring Branch Ln

Approved

Filed Jun 29, 2025 by Sam Okafor, Summit Backflow Testing · paper form read in and confirmed by staff

Report

Date of service
Jun 29, 2025
Assembly type
RP
Serial number
W612322
Size
1
Test gauge serial
G-6522
Gauge calibration date
Sep 22, 2024
Check valve 1
7 psid
Check valve 1 closed tight
Yes
Check valve 2
4 psid
Relief valve opened at
3.9 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Sam Okafor, current on the service date
  • All required fields present
  • Address matches parcel 035-34-01289
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

8162 Spring Branch Ln
Owner: Casey Hollins
Parcel 035-34-01289