Backflow assembly test · 9019 Laurel Rd

Approved

Filed Feb 7, 2025 by Sam Okafor, Summit Backflow Testing · paper form read in and confirmed by staff

Report

Date of service
Feb 7, 2025
Assembly type
DC
Serial number
A780627
Size
1
Test gauge serial
G-5138
Gauge calibration date
Dec 4, 2023
Check valve 1
0.7 psid
Check valve 1 closed tight
No
Check valve 2
2.9 psid
Result
Fail
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 035-68-01118
  • Test gauge calibration is more than a year old.
  • Result: needs follow-up. The property stays on the overdue list until a passing report arrives.

Decision

Approved by Auto-approved (no flags). The property's next due date is set and the owner gets a receipt.

Property

9019 Laurel Rd
Owner: Alex Ramirez
Parcel 035-68-01118