El Paso County, COCompliance reporting portal
Demo · made-up dataOpen the pro appChange county
← Backflow review queue

Backflow assembly test · 4196 Mill Creek Trl

Approved

Filed Jul 5, 2025 by Riley Ramirez, Keystone Plumbing & Backflow · paper form read in and confirmed by staff

Report

Date of service
Jul 5, 2025
Assembly type
RP
Serial number
Z150997
Size
3/4
Test gauge serial
G-7408
Gauge calibration date
Oct 30, 2024
Check valve 1
8.9 psid
Check valve 1 closed tight
Yes
Check valve 2
3.6 psid
Relief valve opened at
4 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 041-30-01270
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.

Property

4196 Mill Creek Trl
Owner: Morgan Stroud
Parcel 041-30-01270