Backflow assembly test · Two Rivers Diner
ApprovedFiled Nov 10, 2026 by Rowan Ellery, Evergreen Plumbing & Backflow · filed from phone
Report
- Date of service
- Nov 10, 2026
- Assembly type
- RP
- Serial number
- Z889356
- Size
- 4
- Test gauge serial
- G-2550
- Gauge calibration date
- Apr 6, 2026
- Check valve 1
- 7.3 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 2.4 psid
- Relief valve opened at
- 3.4 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 041-84-01239
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.