Backflow assembly test · 4605 Ridgeview Dr

Approved

Filed May 28, 2025 by Rowan Pruitt, Summit Backflow Testing · paper form read in and confirmed by staff

Report

Date of service
May 28, 2025
Assembly type
RP
Serial number
B816237
Size
1
Test gauge serial
G-9536
Gauge calibration date
Nov 7, 2024
Check valve 1
6.3 psid
Check valve 1 closed tight
Yes
Check valve 2
3.8 psid
Relief valve opened at
2.9 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 041-90-01008
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.