Backflow assembly test · Crossroads Apartments

Approved

Filed Oct 24, 2025 by Rowan Pruitt, Summit Backflow Testing · filed from phone

Report

Date of service
Oct 24, 2025
Assembly type
RP
Serial number
K783938
Size
1
Test gauge serial
G-1253
Gauge calibration date
May 20, 2025
Check valve 1
6.8 psid
Check valve 1 closed tight
Yes
Check valve 2
3.9 psid
Relief valve opened at
3.9 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file for Rowan Pruitt, current on the service date
  • All required fields present
  • Address matches parcel 041-15-01139
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by Auto-approved (no flags). The property's next due date is set and the owner gets a receipt.

Property

7938 Quarry Way
Owner: Ellery Holdings LLC
Parcel 041-15-01139