El Paso County, COCompliance reporting portal
Demo · made-up dataOpen the pro appChange county
← Backflow review queue

Backflow assembly test · 1213 Sycamore Rd

Approved

Filed Oct 17, 2024 by Rowan Ellery, Evergreen Plumbing & Backflow · paper form read in and confirmed by staff

Report

Date of service
Oct 17, 2024
Assembly type
RP
Serial number
Z218301
Size
1
Test gauge serial
G-1238
Gauge calibration date
May 14, 2024
Check valve 1
3.8 psid
Check valve 1 closed tight
Yes
Check valve 2
2 psid
Relief valve opened at
3.1 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 041-67-01098
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

1213 Sycamore Rd
Owner: Quinn Harlow
Parcel 041-67-01098