Backflow assembly test · 9739 Stone Gate Rd
ApprovedFiled Jun 29, 2026 by Rowan Pruitt, Summit Backflow Testing · filed from phone
Report
- Date of service
- Jun 29, 2026
- Assembly type
- PVB
- Serial number
- W583839
- Size
- 3/4
- Test gauge serial
- G-4648
- Gauge calibration date
- Mar 5, 2026
- Check valve 1
- 8.2 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 2.8 psid
- Result
- Repaired and passed
- Repairs made
- Replaced check valve 1 rubber
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 041-61-01177
- Readings in range, no flags
- Result: passing. Next due date resets when approved.