← Backflow review queue
Backflow assembly test · Golden Apartments
ApprovedFiled Oct 6, 2024 by Rowan Pruitt, Summit Backflow Testing · filed from phone
Report
- Date of service
- Oct 6, 2024
- Assembly type
- RP
- Serial number
- Z822609
- Size
- 2
- Test gauge serial
- G-8375
- Gauge calibration date
- Jan 17, 2024
- Check valve 1
- 7.2 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 2.4 psid
- Relief valve opened at
- 3.8 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 041-33-01055
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.
Property
3188 Cedar Hollow Ln
Owner: Brandt Holdings LLC
Parcel 041-33-01055