Backflow assembly test · 2680 Stone Gate Ct
ApprovedFiled Nov 16, 2024 by Riley Ramirez, Keystone Plumbing & Backflow · filed from phone
Report
- Date of service
- Nov 16, 2024
- Assembly type
- RP
- Serial number
- A777307
- Size
- 1
- Test gauge serial
- G-7677
- Gauge calibration date
- May 7, 2024
- Check valve 1
- 8.3 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 2.5 psid
- Relief valve opened at
- 3.1 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Riley Ramirez, current on the service date
- All required fields present
- Address matches parcel 041-72-01294
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by J. Staff. The property's next due date is set and the owner gets a receipt.
Property
2680 Stone Gate Ct
Owner: Hayden Pruitt
Parcel 041-72-01294