Backflow assembly test · 8238 Ridgeview Ct
ApprovedFiled Aug 5, 2025 by Rowan Pruitt, Summit Backflow Testing · filed from phone
Report
- Date of service
- Aug 5, 2025
- Assembly type
- RP
- Serial number
- W575762
- Size
- 1
- Test gauge serial
- G-2821
- Gauge calibration date
- Feb 22, 2025
- Check valve 1
- 7.6 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 1.5 psid
- Relief valve opened at
- 2.5 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Rowan Pruitt, current on the service date
- All required fields present
- Address matches parcel 041-93-01344
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by J. Staff. The property's next due date is set and the owner gets a receipt.