Gilpin County, COCompliance reporting portal
Demo · made-up dataOpen the pro appChange county
← Backflow review queue

Backflow assembly test · Golden Medical Offices

Approved

Filed Jul 5, 2024 by Blake Kessler, Keystone Plumbing & Backflow · filed from phone

Report

Date of service
Jul 5, 2024
Assembly type
DC
Serial number
B993089
Size
1 1/2
Test gauge serial
G-6803
Gauge calibration date
Oct 7, 2023
Check valve 1
7.4 psid
Check valve 1 closed tight
Yes
Check valve 2
2.3 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 047-39-01151
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by Auto-approved (no flags). The property's next due date is set and the owner gets a receipt.

Property

6529 Meadow Lark Ct
Owner: Fairley Holdings LLC
Parcel 047-39-01151