Gilpin County, COCompliance reporting portal
Demo · made-up dataOpen the pro appChange county
← Backflow review queue

Backflow assembly test · 7997 Spring Branch Ln

Approved

Filed Oct 17, 2024 by Blake Kessler, Keystone Plumbing & Backflow · filed from phone

Report

Date of service
Oct 17, 2024
Assembly type
DC
Serial number
A673406
Size
3/4
Test gauge serial
G-4886
Gauge calibration date
Jun 29, 2024
Check valve 1
8.2 psid
Check valve 1 closed tight
Yes
Check valve 2
3.2 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 047-61-01071
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.

Property

7997 Spring Branch Ln
Owner: Shawn Nguyen
Parcel 047-61-01071