Jefferson County, COCompliance reporting portal
Demo · made-up dataOpen the pro appChange county
← Backflow review queue

Backflow assembly test · Main Street Elementary School

Approved

Filed Jun 12, 2024 by Riley Marsh, Valley Backflow Testing · filed from phone

Report

Date of service
Jun 12, 2024
Assembly type
RP
Serial number
Z600820
Size
1
Test gauge serial
G-9859
Gauge calibration date
Apr 7, 2023
Check valve 1
0 psid
Check valve 1 closed tight
No
Check valve 2
1.3 psid
Relief valve opened at
3.7 psid
Result
Fail
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 059-95-01038
  • Test gauge calibration is more than a year old.
  • Result: needs follow-up. The property stays on the overdue list until a passing report arrives.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.

Property

1089 Stone Gate Trl
Owner: Okafor Holdings LLC
Parcel 059-95-01038