← Backflow review queue
Backflow assembly test · Main Street Elementary School
ApprovedFiled Jul 15, 2025 by Cameron Okafor, Valley Backflow Testing · filed from phone
Report
- Date of service
- Jul 15, 2025
- Assembly type
- RP
- Serial number
- Z600820
- Size
- 1
- Test gauge serial
- G-1733
- Gauge calibration date
- Sep 30, 2024
- Check valve 1
- 6.9 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 3.3 psid
- Relief valve opened at
- 1.8 psid
- Result
- Repaired and passed
- Repairs made
- Replaced check valve 1 rubber
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 059-95-01038
- RP relief valve must open at 2.0 psid or more.
- Result: passing. Next due date resets when approved.
Decision
Approved by J. Staff. The property's next due date is set and the owner gets a receipt.
Property
1089 Stone Gate Trl
Owner: Okafor Holdings LLC
Parcel 059-95-01038