Jefferson County, COCompliance reporting portal
Demo · made-up dataOpen the pro appChange county
← Backflow review queue

Backflow assembly test · Main Street Elementary School

Approved

Filed Aug 12, 2026 by Quinn Calloway, Evergreen Plumbing & Backflow · paper form read in and confirmed by staff

Report

Date of service
Aug 12, 2026
Assembly type
RP
Serial number
Z600820
Size
1
Test gauge serial
G-9287
Gauge calibration date
Oct 20, 2025
Check valve 1
5.6 psid
Check valve 1 closed tight
Yes
Check valve 2
1.2 psid
Relief valve opened at
3.2 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 059-95-01038
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.

Property

1089 Stone Gate Trl
Owner: Okafor Holdings LLC
Parcel 059-95-01038