Backflow assembly test · 6691 Fox Run Trl
ApprovedFiled Mar 16, 2025 by Riley Marsh, Valley Backflow Testing · paper form read in and confirmed by staff
Report
- Date of service
- Mar 16, 2025
- Assembly type
- DC
- Serial number
- A675534
- Size
- 3/4
- Test gauge serial
- G-2723
- Gauge calibration date
- Jul 31, 2024
- Check valve 1
- 8.3 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 1.6 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 059-49-01084
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by J. Staff. The property's next due date is set and the owner gets a receipt.