← Backflow review queue
Backflow assembly test · Hilltop Car Wash
ApprovedFiled Apr 18, 2025 by Sam Marsh, Evergreen Plumbing & Backflow · filed from phone
Report
- Date of service
- Apr 18, 2025
- Assembly type
- RP
- Serial number
- W266417
- Size
- 1
- Test gauge serial
- G-5760
- Gauge calibration date
- Dec 29, 2024
- Check valve 1
- 0.3 psid
- Check valve 1 closed tight
- No
- Check valve 2
- 3.5 psid
- Relief valve opened at
- 3.3 psid
- Result
- Fail
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Sam Marsh, current on the service date
- All required fields present
- Address matches parcel 059-40-01022
- Readings in range, no flags
- Result: needs follow-up. The property stays on the overdue list until a passing report arrives.
Decision
Approved by Auto-approved (no flags). The property's next due date is set and the owner gets a receipt.
Property
8557 Mill Creek Ct
Owner: Stroud Holdings LLC
Parcel 059-40-01022