Jefferson County, COCompliance reporting portal
Demo · made-up dataOpen the pro appChange county
← Backflow review queue

Backflow assembly test · 4235 Pine Knoll Ln

Approved

Filed Sep 20, 2026 by Riley Marsh, Valley Backflow Testing · paper form read in and confirmed by staff

Report

Date of service
Sep 20, 2026
Assembly type
RP
Serial number
Z852073
Size
1
Test gauge serial
G-9248
Gauge calibration date
Dec 8, 2025
Check valve 1
4.6 psid
Check valve 1 closed tight
Yes
Check valve 2
2.3 psid
Relief valve opened at
1.1 psid
Result
Repaired and passed
Repairs made
Replaced check valve 1 rubber
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 059-20-01151
  • RP relief valve must open at 2.0 psid or more.
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

4235 Pine Knoll Ln
Owner: Quinn Lindqvist
Parcel 059-20-01151