← Backflow review queue
Backflow assembly test · Maple Leaf Self Storage
ApprovedFiled May 17, 2026 by Cameron Calloway, Evergreen Plumbing & Backflow · filed from phone
Report
- Date of service
- May 17, 2026
- Assembly type
- RP
- Serial number
- K546889
- Size
- 1
- Test gauge serial
- G-8672
- Gauge calibration date
- Mar 4, 2026
- Check valve 1
- 4.1 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 3.3 psid
- Relief valve opened at
- 2.6 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 059-79-01159
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by J. Staff. The property's next due date is set and the owner gets a receipt.
Property
6486 Stone Gate Ln
Owner: Fairley Holdings LLC
Parcel 059-79-01159