← Backflow review queue
Backflow assembly test · Crossroads Elementary School
ApprovedFiled Aug 20, 2025 by Riley Marsh, Valley Backflow Testing · filed from phone
Report
- Date of service
- Aug 20, 2025
- Assembly type
- RP
- Serial number
- W293830
- Size
- 2
- Test gauge serial
- G-2494
- Gauge calibration date
- Nov 13, 2024
- Check valve 1
- 3.6 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 2.4 psid
- Relief valve opened at
- 2.7 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 059-41-01283
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by Auto-approved (no flags). The property's next due date is set and the owner gets a receipt.
Property
1667 Stone Gate Ln
Owner: Benton Holdings LLC
Parcel 059-41-01283