Jefferson County, COCompliance reporting portal
Demo · made-up dataOpen the pro appChange county
← Backflow review queue

Backflow assembly test · 661 Stone Gate Ln

Approved

Filed May 22, 2025 by Cameron Calloway, Evergreen Plumbing & Backflow · paper form read in and confirmed by staff

Report

Date of service
May 22, 2025
Assembly type
RP
Serial number
W712637
Size
3/4
Test gauge serial
G-9408
Gauge calibration date
Sep 30, 2024
Check valve 1
3.5 psid
Check valve 1 closed tight
Yes
Check valve 2
2.8 psid
Relief valve opened at
1.6 psid
Result
Repaired and passed
Repairs made
Replaced check valve 1 rubber
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 059-10-01063
  • RP relief valve must open at 2.0 psid or more.
  • Result: passing. Next due date resets when approved.

Decision

Approved by Auto-approved (no flags). The property's next due date is set and the owner gets a receipt.

Property

661 Stone Gate Ln
Owner: Avery Ashby
Parcel 059-10-01063