← Backflow review queue
Backflow assembly test · 7908 Hickory Ln
ApprovedFiled Jan 12, 2026 by Cameron Okafor, Valley Backflow Testing · paper form read in and confirmed by staff
Report
- Date of service
- Jan 12, 2026
- Assembly type
- RP
- Serial number
- B454833
- Size
- 3/4
- Test gauge serial
- G-7142
- Gauge calibration date
- May 2, 2025
- Check valve 1
- 5.9 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 1.1 psid
- Relief valve opened at
- 2.3 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 059-69-01272
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by J. Staff. The property's next due date is set and the owner gets a receipt.
Property
7908 Hickory Ln
Owner: Riley Ashby
Parcel 059-69-01272