Larimer County, COCompliance reporting portal
Demo · made-up dataOpen the pro appChange county
← Backflow review queue

Backflow assembly test · Riverside Grill

Approved

Filed Jun 1, 2024 by Hayden Ramirez, Patriot Backflow Testing · filed from phone

Report

Date of service
Jun 1, 2024
Assembly type
RP
Serial number
W538974
Size
1
Test gauge serial
G-8949
Gauge calibration date
Oct 24, 2023
Check valve 1
8.1 psid
Check valve 1 closed tight
Yes
Check valve 2
1.6 psid
Relief valve opened at
2.4 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 069-18-01118
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by Auto-approved (no flags). The property's next due date is set and the owner gets a receipt.

Property

7411 Old Church Rd
Owner: Harlow Holdings LLC
Parcel 069-18-01118