Larimer County, COCompliance reporting portal
Demo · made-up dataOpen the pro appChange county
← Backflow review queue

Backflow assembly test · Blue Heron Diner

Approved

Filed Oct 28, 2025 by Blake Marsh, Heritage Backflow Testing · filed from phone

Report

Date of service
Oct 28, 2025
Assembly type
RP
Serial number
W980831
Size
1
Test gauge serial
G-5307
Gauge calibration date
Apr 19, 2025
Check valve 1
4.7 psid
Check valve 1 closed tight
Yes
Check valve 2
2.9 psid
Relief valve opened at
2.2 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 069-16-01277
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.

Property

100 Spring Branch Ct
Owner: Harlow Holdings LLC
Parcel 069-16-01277