Larimer County, COCompliance reporting portal
Demo · made-up dataOpen the pro appChange county
← Backflow review queue

Backflow assembly test · Riverside Medical Offices

Approved

Filed Feb 21, 2026 by Hayden Ramirez, Patriot Backflow Testing · filed from phone

Report

Date of service
Feb 21, 2026
Assembly type
RP
Serial number
W432883
Size
2
Test gauge serial
G-7090
Gauge calibration date
Sep 24, 2025
Check valve 1
5.6 psid
Check valve 1 closed tight
Yes
Check valve 2
2.4 psid
Relief valve opened at
3.6 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 069-24-01337
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by Auto-approved (no flags). The property's next due date is set and the owner gets a receipt.

Property

6171 Orchard Rd
Owner: Ramirez Holdings LLC
Parcel 069-24-01337