Report

Date of service
Nov 26, 2026
Assembly type
RP
Serial number
W172333
Size
4
Test gauge serial
G-8296
Gauge calibration date
Jul 2, 2026
Check valve 1
7.3 psid
Check valve 1 closed tight
Yes
Check valve 2
1.7 psid
Relief valve opened at
2.5 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 069-20-01009
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Property

3652 Turkey Hill Way
Owner: Marsh Holdings LLC