Larimer County, COCompliance reporting portal
Demo · made-up dataOpen the pro appChange county
← Backflow review queue

Backflow assembly test · 5875 Turkey Hill Way

Approved

Filed Oct 14, 2023 by Hayden Ramirez, Patriot Backflow Testing · filed from phone

Report

Date of service
Oct 14, 2023
Assembly type
RP
Serial number
B786104
Size
3/4
Test gauge serial
G-7167
Gauge calibration date
Feb 22, 2023
Check valve 1
8.8 psid
Check valve 1 closed tight
Yes
Check valve 2
1.5 psid
Relief valve opened at
3.2 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 069-69-01241
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.

Property

5875 Turkey Hill Way
Owner: Logan Marsh
Parcel 069-69-01241