Larimer County, COCompliance reporting portal
Demo · made-up dataOpen the pro appChange county
← Backflow review queue

Backflow assembly test · 2411 Orchard Ln

Approved

Filed May 7, 2026 by Hayden Ramirez, Patriot Backflow Testing · filed from phone

Report

Date of service
May 7, 2026
Assembly type
RP
Serial number
W710145
Size
1
Test gauge serial
G-7940
Gauge calibration date
Aug 8, 2025
Check valve 1
5.3 psid
Check valve 1 closed tight
Yes
Check valve 2
3.6 psid
Relief valve opened at
3.3 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 069-87-01031
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

2411 Orchard Ln
Owner: Jamie Harlow
Parcel 069-87-01031