Backflow assembly test · Crossroads Elementary School
ApprovedFiled Nov 5, 2026 by Jordan Harlow, Northstar Plumbing & Backflow · filed from phone
Report
- Date of service
- Nov 5, 2026
- Assembly type
- RP
- Serial number
- A278769
- Size
- 1 1/2
- Test gauge serial
- G-6093
- Gauge calibration date
- Jan 12, 2026
- Check valve 1
- 6.1 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 1.3 psid
- Relief valve opened at
- 3.1 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 077-35-01133
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by J. Staff. The property's next due date is set and the owner gets a receipt.