Backflow assembly test · 4430 Old Church Ln
ApprovedFiled Jan 14, 2026 by Parker Okafor, Ridge Plumbing & Backflow · filed from phone
Report
- Date of service
- Jan 14, 2026
- Assembly type
- RP
- Serial number
- A477413
- Size
- 3/4
- Test gauge serial
- G-1781
- Gauge calibration date
- Sep 22, 2025
- Check valve 1
- 8.8 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 3.5 psid
- Relief valve opened at
- 3.5 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file for Parker Okafor, current on the service date
- All required fields present
- Address matches parcel 077-37-01101
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by Auto-approved (no flags). The property's next due date is set and the owner gets a receipt.
Property
4430 Old Church Ln
Owner: Emerson Ramirez
Parcel 077-37-01101