Mesa County, COCompliance reporting portal
Demo · made-up dataOpen the pro appChange county
← Backflow review queue

Backflow assembly test · 7774 Meadow Lark Ln

Approved

Filed Sep 5, 2024 by Hayden Benton, Northstar Plumbing & Backflow · filed from phone

Report

Date of service
Sep 5, 2024
Assembly type
RP
Serial number
W438495
Size
3/4
Test gauge serial
G-5880
Gauge calibration date
Apr 5, 2024
Check valve 1
3.4 psid
Check valve 1 closed tight
Yes
Check valve 2
2.3 psid
Relief valve opened at
2.4 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 077-75-01305
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

7774 Meadow Lark Ln
Owner: Rowan Danner
Parcel 077-75-01305