Mesa County, COCompliance reporting portal
Demo · made-up dataOpen the pro appChange county
← Backflow review queue

Backflow assembly test · 6839 Quarry Ln

Approved

Filed Jun 9, 2024 by Morgan Calloway, Ridge Plumbing & Backflow · filed from phone

Report

Date of service
Jun 9, 2024
Assembly type
DC
Serial number
K136109
Size
3/4
Test gauge serial
G-8388
Gauge calibration date
Sep 8, 2023
Check valve 1
3.4 psid
Check valve 1 closed tight
Yes
Check valve 2
1.1 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 077-21-01259
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by Auto-approved (no flags). The property's next due date is set and the owner gets a receipt.

Property

6839 Quarry Ln
Owner: Rowan Vance
Parcel 077-21-01259