← Backflow review queue
Backflow assembly test · 2544 Fox Run Dr
ApprovedFiled Oct 22, 2024 by Morgan Calloway, Ridge Plumbing & Backflow · paper form read in and confirmed by staff
Report
- Date of service
- Oct 22, 2024
- Assembly type
- PVB
- Serial number
- W466038
- Size
- 3/4
- Test gauge serial
- G-3710
- Gauge calibration date
- May 20, 2024
- Check valve 1
- 7.4 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 3.6 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 077-30-01213
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by Auto-approved (no flags). The property's next due date is set and the owner gets a receipt.
Property
2544 Fox Run Dr
Owner: Morgan Marsh
Parcel 077-30-01213